Standard TS35 DIN Rail in accordance with EN 60715
Wire
Input / Output: AWG 20-14
Protection Structure
-
Terminal
-
Unit Weight
0.22 kg (0.49 lb)
Dimensions
100 x 32 x
100.6 mm 3.94” x
1.26” x
3.96”
Vibration (Operating)
-
Shock Test (Operating)
-
Operating Temperature
-20°C to +70°C
Storage Temperature
-25°C to +85°C
Power De-rating
Vertical / Horizontal: -20ºC to -10ºC de-rate power by 1% / ºC, -10ºC to 0ºC de-rate power by 2% / ºC, > 50ºC de-rate power by 2.5% / ºC
Operating Humidity
5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)
IEC60068-2-27, 30G (300m/S for a duration of 18ms, 1 times per direction, 2 times in total
Vibration (Non-Operating)
IEC60068-2-6, 10Hz to 150Hz @ 50m/S² (5G peak); 90 min per axis for all X, Y, Z direction
Storage Humidity
-
Operating Altitude
0 to 2,000 Meters (6,560 ft)
Pollution Degree
2
Bump Test (Operating)
IEC 60068-2-29, Half Sine Wave: 10G for a duration of 11ms, 1,000 times per direction, 6,000 times in total
Over Voltage Category
III According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances)
Corrosion
-
Overvoltage
< 32.4V, SELV Output, Latch Mode
Overload / Overcurrent
> 105~180% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery)
Over Temperature
< 75°C Surrounding Air Temperature @ 100% load, Latch Mode
Short Circuit
Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
Reverse Polarity Protection
-
Degree of Protection
-
Protection Against Shock
Class I with Primary Earth connection
Input Polarity Protection
-
Battery Polarity Protection
-
Wrong Battery Voltage Protection
-
Deep Discharge Protection
-
Overload
-
Overcurrent
-
Internal Fuse
-
Insufficient Input Voltage Protection
-
MTBF
> 500,000 hrs. as per Telcordia SR-332 (I/P: 115Vac, O/P: 100% load, Ta: 25°C)
Expected Cap Life Time
10 years (115Vac & 230Vac, 50% load @ 40°C)
Safety Certificate
-
Electrical Safety
SIQ Bauart: EN 60950-1, EN 62368-1 UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395), UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) CB scheme: IEC 60950-1, IEC 62368-1 UKCA : BS EN 62368-1
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
Medical Safety
-
Galvanic Isolation
Input to Output: 3.0KVac Input to Ground: 1.5KVac Output to Ground: 0.5KVac
Industrial Control Equipment
UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355) CSA: CSA C22.2 No. 107.1-01 (File No. 181564)
Hazardous Location / ATEX
-
II 3 G ATEX 2014/34/EU
-
Electrical Equipments of Machines
EN 60204-1 (over voltage category III)
Electrical Equipment for Use in Electrical Power Installations
IEC/EN/BS EN 62477-1
Safety Entry Low Voltage
SELV (IEC 60950-1)
Maritime
-
Material and Parts
-
Isolation Resistance
-
PE Resistance
-
UKCA
In conformance with 2016 No. 1101. The Electrical Equipment (Safety) Regulations 2016 and 2016 No. 1091 The Electromagnetic Compatibility Regulations 2016
Certificates for Other Countries
-
BIS
-
KC
-
Electrical Equipment for Measurement, Control, and Laboratory Use
-
ITE Safety
-
SIL3
-
Emission
(CE & RE) Generic Standards: CISPR32, EN/BS EN 55032, KN 32 CISPR11, EN/BS EN 55011, FCC Title 47: Class B
Immunity
Generic Standards: EN/BS EN 55024, KN 35, EN/BS EN 61000-6-2
Be the first to hear about new events, news and products!
Subscribe to our newsletter
Be the first to hear about new events, news and products!
Subscribe
Subscribe to DeltaPSU newsletter and be the first to know about our new product releases and industry knowledge. Read our Privacy Policy.
Marketing Permissions*
DeltaPSU will use the information you provide on this form to be in touch with you.
To unsubscribe, click the link in our newsletter. We will treat your data with respect.
We use cookies to provide the best user experience for those who visit our website. By using this website you agree to the placement of cookies and our Privacy Policy. Accept