Delta Electronics adds two Redundancy Modules, DRR-20A and DRR-40A to its CliQ II series of DIN Rail power management products. They are compatible with both 24Vdc and 48Vdc power supplies, offering redundancy functionality. These modules can also be used for Parallel operation.
The Redundancy function ensures zero system down time for the customer when one of the power supply fails or is being disconnected unexpectedly. Under normal circumstances, both power supplies are each operating at approximately 50% load. When one fails, the other automatically takes over, thus providing 100% load, and ensures that the system continues running
The fault relay function alerts the user of any failure through potential free contacts. The LED lights on the Redundancy Modules also indicate the health of each individual power supply.
How to Install CliQ II 24Vdc Redundancy Module:
Step 1.
Measure the output voltages at no load from Vin 1 to Com i.e. Voltage Vin 1 to Com and Voltage Vin 2 to Com of Redundancy module. If the voltages are not the same, follow Step 2. If same, skip to Step 3.
Step 2.
Adjust the
output voltages, with the help of VR on the Power Supply front panel
marked as ADJUST, to the same level. For example, if PSU 1 is measuring
24.15Vdc and PSU 2 is measuring 24.25Vdc, adjust the output voltage of
one to be the same as the other.
Step 3.
Connect the
PSU to the end system load and measure the output voltages from Vin 1 to
Com i.e. Voltage Vin 1 to Com and Voltage Vin 2 to Com of Redundancy
module. Ensure that the output voltages are the same even after the 2
Power Supplies are connected to load. If not, adjust them as described
in Step 2. A difference of both PSU ± 25mV is acceptable.
*The Redundancy Modules can be used for all PMC 24V, CliQ 24V, CliQ II 24V and 48V models.