> 60°C de-rate power by 2.5% / °C (when battery is fully charged) If the battery is not fully charged at max load, it is recommended that the surrounding air temperature should not exceed 50°C.
運行濕度
5 to 95% RH (Non-Condensing)
衝擊測試(非運行狀態)
IEC 60068-2-27, 30 G (300 m/s²) for a duration of 18 ms, 1 time per direction, 2 times in total
振動測試(非運行狀態)
IEC 60068-2-6, 10 Hz to 500 Hz @ 30 m/s² (3 G peak); 60 min per axis for all X, Y, Z direction
儲藏濕度
-
運行高度
0 to 6,000 m (Approvals apply only up to 5,000 m)
污染程度
2
碰撞試驗(運行狀態)
-
過壓類別
-
Corrosion
-
過壓保護
Auto Recovery
超負載/過電保護
Normal Operation: Auto Recovery Battery Operation: Latch off
過溫保護
Normal Operation: Auto Recovery Battery Operation: Latch off
短路保護
-
極性反接保護
-
防護等級
IP20
電擊防護等級
Class III
輸入端極性保護
Yes
電池極性保護
Yes
電池電壓保護錯誤
Yes, 30 Vdc Max (the maximum voltage that will not cause damage to the unit)
深度放電保護
Yes (21 V typ.)
超負載保護
-
過電保護
-
內部保險絲
-
Insufficient Input Voltage Protection
Yes
MTBF
> 500,000 hrs. as per Telcordia SR-332
預計最長使用壽命
-
Safety Certificate
-
電氣安全
CB scheme: IEC 62368-1 TUV Bauart: EN 62368-1 UL/cUL recognized: UL 62368-1 and CAN/CSA C22.2 No. 62368-1 (File No. E131881) EAC: TP TC 002/2011
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
醫療安全
-
電隔離
Power Port to Housing: 500 Vac Signal Port to Housing: 500 Vac Power Port to Signal Port: 500 Vac
工業控制設備
-
危險場所/ATEX
-
II 3 G ATEX 2014/34/EU
-
機器電氣設備
-
用於電率安裝的電氣設備
-
安全特低電壓
-
海事
-
材料與部件
-
隔離電阻
-
PE 電阻
-
UKCA
In conformance with Electromagnetic Compatibility Regulations 2016 and Electrical Equipment (Safety) Regulations 2016
國家地區證書
-
BIS
-
KC
-
Electrical Equipment for Measurement, Control, and Laboratory Use
-
ITE Safety
-
SIL3
-
輻射與傳導
CE & RE EN/BS EN 61000-6-4, EN 61204-3
抗擾度
EN/BS EN 61000-6-2, EN 61204-3
諧波電流排放
-
電壓波動和閃變
-
ESD 抗擾度
-
輻射抗擾度
-
EFT
-
電湧
-
傳導抗擾度
-
磁場
-
電壓驟降
-
通用用途之部件供電
-
額定電池電壓
24 Vdc, SLA Sealed lead acid battery 2 x 12 Vdc, SLA Sealed lead acid battery in series
電池電壓範圍
-
電池容量
3.4 AH ~ 100 AH
電池充電模式
-
充電電壓結束
27.6 V
電池熔斷器
-
電池放電電壓範圍
21 Vdc ... 27.6 Vdc 30 Vdc Max (the maximum voltage that will not cause damage to the unit)