Click the link below to download the file.
Get your files as below link
Dowload link
24V
211W
8.8A
90-132Vac, 180-264Vac (Selectable by Switch)
215 x 115 x 50 mm
8.46” x 4.53” x 1.97”
0.63 kg (1.39 lb)
24V
211W
8.8A
90-132Vac, 180-264Vac (Selectable by Switch)
215 x 115 x 50 mm
8.46” x 4.53” x 1.97”
0.63 kg (1.39 lb)
Output Current
8.8A
|
Output Voltage
24V
|
Output Voltage Range
|
Output Voltage Adjustment Range
21.6-26.4Vdc
|
Output Power
211W
|
Output Current Adjustment Range
|
Max Output Voltage
|
Buffering Time
-
|
Line Regulation
± 0.5% typ. (@ 100-132Vac & 200-264Vac)
|
Load Regulation
± 0.5% typ. (@ 100-132Vac & 200-264Vac )
|
PARD
< 150mVpp
|
Start-up Time
1000ms typ. @ 115Vac & 230Vac (100% load)
|
Hold-up Time
20ms typ. @ 115Vac,
24ms typ. @ 230Vac |
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 0-100% load
|
Start-up with Capacitive Loads
8,000µF Max
|
Remote ON/OFF
-
|
Protective Device
-
|
Voltage Drop Between Input and Output
-
|
Residual Ripple/PARD (20MHz)
-
|
Residual Ripple
-
|
Max. Power
-
|
Ripple & Noise
-
|
LED System Voltage Range in CC Mode
-
|
Rise Time
30ms typ. @ 115Vac, 20ms typ. @ 230Vac (100% load)
|
Nominal Input Voltage
100-120Vac, 200-240Vac (Selectable by Switch)
|
Input Voltage Range
90-132Vac, 180-264Vac (Selectable by Switch)
|
Max Input Voltage
-
|
Nominal Input Frequency
50-60Hz
|
Input Frequency Range
47-63Hz
|
Nominal DC Input Voltage
|
DC Input Voltage Range
-
|
Input Current
< 4.50A @ 115Vac,
< 2.50A @ 230Vac |
Input Power (Standby Mode)
-
|
Efficiency at 100% load
> 88.5% @ 230Vac
|
Max Inrush Current
< 55A @ 230Vac
|
Charging Time
-
|
Power Factor at 100% load
-
|
Leakage Current
< 0.25mA @ 240Vac
|
Nominal Current
-
|
Total Harmonic Distortion
-
|
Max Power Dissipation
-
|
Case Chassis / Cover
Aluminium
|
|
Indicator
-
|
|
Cooling System
Convection
|
|
Input Terminal
-
|
|
Output Terminal
-
|
|
Signal Terminal
-
|
|
Noise Sound Pressure Level (SPL)
-
|
|
Input/Output Terminal
-
|
|
Signal
-
|
|
Mounting Rail
-
|
|
Wire
-
|
|
Protection Structure
-
|
|
Unit Weight
0.63 kg (1.39 lb)
|
Dimensions
215 x 115 x
50 mm
8.46” x 4.53” x 1.97” |
Vibration (Operating)
-
|
Shock Test (Operating)
-
|
Operating Temperature
-10°C to +60°C (Cold start at -20°C)
|
Storage Temperature
-25°C to +85°C
|
Power De-rating
> 40°C de-rate power by 2.5% / °C
< 100Vac de-rate power by 3% / 1V |
Operating Humidity
5-95% RH (Non-Condensing)
|
Shock Test (Non-Operating)
IEC 60068-2-27, Half Sine: 50G for a duration of 11ms, 3 times for each 3 directions
|
Vibration (Non-Operating)
IEC 60068-2-6, Random: 5Hz to 500Hz @ 2.09Grms, 20 min per axis for all X, Y, Z direction
|
Storage Humidity
-
|
Operating Altitude
0 to 5,000 Meters (16,400 ft.)
|
Pollution Degree
2
|
Bump Test (Operating)
-
|
Over Voltage Category
II
|
Overvoltage
27.6-32.4V, Hicc-up Mode, Non-Latching (Auto-Recovery)
|
Overload / Overcurrent
105-150%, Hicc-up Mode, Non-Latching (Auto-Recovery)
|
Over Temperature
Hicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed)
|
Short Circuit
Hicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed)
|
Reverse Polarity Protection
-
|
Degree of Protection
-
|
Protection Against Shock
Class I with PE connection
|
Input Polarity Protection
-
|
Battery Polarity Protection
-
|
Wrong Battery Voltage Protection
-
|
Deep Discharge Protection
-
|
Overload
-
|
Overcurrent
-
|
MTBF
> 700,000 hrs. as per Telcordia SR-332
I/P: 100Vac, O/P: 100% load, Ta: 35°C |
Expected Cap Life Time
10 years (115Vac & 230Vac, 50% load @ 40°C)
|
Safety Certificate
-
|
Electrical Safety
UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1
UL 62368-1 and CSA C22.2 No. 62368-1 CB scheme: IEC 60950-1, IEC 62368-1 |
CE
-
|
Medical Safety
-
|
Galvanic Isolation
Input to Output: 3.0KVac
Input to Ground: 1.5KVac Output to Ground: 0.5KVac |
Industrial Control Equipment
-
|
Hazardous Location / ATEX
-
|
II 3 G ATEX 2014/34/EU
-
|
Electrical Equipments of Machines
-
|
Electrical Equipment for Use in Electrical Power Installations
-
|
Safety Entry Low Voltage
SELV (EN 60950-1)
|
Maritime
-
|
Material and Parts
-
|
Isolation Resistance
-
|
PE Resistance
-
|
Emission
(CE & RE)
CISPR 32, EN 55032, FCC Title 47: Class A (With Delta EMI filter P/N: 10DKAW5) |
Immunity
EN 55024
|
Harmonic Current Emissions
-
|
Voltage Fluctuation and Flicker
-
|
ESD Immunity
-
|
Radiated Immunity
-
|
EFT
-
|
Surge
-
|
Conducted Immunity
-
|
Magnetic Field
-
|
Voltage Dips
-
|
Component Power Supply for General Use
-
|
12V
240W
20A
90-264 Vac
48V
320W
6.7A
90-264 Vac
12V
320W
26.7A
90-264 Vac
24V
240W
10A
90-264 Vac
Subscribe to DeltaPSU newsletter and be the first to know about our new product releases and industry knowledge. Read our Privacy Policy.
DeltaPSU will use the information you provide on this form to be in touch with you.